Sunday, 14 January 2018

Motor control Centre specifications

motor control center (MCC) is an assembly of one or more enclosed sections having a common power bus and principally containing motor control units. Motor control centers are in modern practice a factory assembly of several motor starters.

Motor control centre specifications

Following are the general specifications for MCC panel. End user can update the specification as per specific requirement.

 1. Refer scheme drawings for wiring details of each feeder or feeder type. Scheme drawings are guidelines and following details shall be met.

a. Ammeter for motor feeders shall be part of display unit
b. Motor space heater power supply (interlocked type) MCB shall be provided for motor feeders rated 45kW and above.
c. Earth leakage relay & CBCT shall be provided for all motor feeders
d. Thermister relay (may be part of micrprocessor based OLR) shall be provided for motor feeders rated 75kW and above.
e. For high inertia loads such as fans, blowers, compressor etc.relay shall be provided proper trip curve to avoid nuisance trip during starting.
f. Direct on line starters shall be provided for motors rated up to and including 22kW. Star delta starters shall be provided for the motors rated 30kW and above.

2. Stud type terminals along with nut and bolt shall be provided in the feeders cable size of 16 sq.mm or more will be terminated. All terminals blocks shall be fingure touch proof.

3. The sleeves of busbar shall be of heat shrinkable PVC material. The busbar joints shall be shrouded.

4. Control supply required for each motor feeder shall be tapped before switch using SP MCB & neutral link.

5. Termination of the cables on any feeder terminals shall be safely possible when other feeder of the same cable alley are live. For this purpose, the feeder terminals shall be segregated with hylam sheet and staggered

6. Unused vacant modules shall be fully equipped with hinged door.

7. MCC shall be complete with inter-panel wiring including the necessary wiring between shipping sections.

8. All switches shall be interlocked with door and have defeat interlock mechanism.  Switches shall have also padlocking facility in OFF position.

9. Removable undrilled gland plate shall be provided at bottom of each panel. Distance between gland plate and cable terminals shall be 800 mm minimum for incomer feeders and 400 mm minimum for outgoing feeders.

10. Indicating lamps for motor ON, OFF and TRIP, earth leakage indication and an emergency STOP push button shall be provided on door of each motor starter feeder as per scheme diagrams.

11. Bill of material of each MCC type of feeder and each kW shall be submitted separately for approval. 

12. Cable clamping supports to be provided in cable alley.

13. Stop PB for each starter feeder shall be mushroom head stayput type.

14. Vendor shall provide marashalling panel with terminals for each motor starter module and interpanel wiring from individual module to these terminals. Marshalling panel shall be provided for all MCCs. Marshalling box to be provided one per shipping section of the MCC.

15. Vendor shall provide cables from each feeder module upto corresponding terminal in marshalling box. Feeder side of this cable shall be terminated at factory & marshalling box side of this cable shall be tagged & kept loose which shall be terminated as per marshalling box termination schedule submitted by MCC vendor. This site work at site shall be done by MCC vendor person.

16. Vendor shall try to provide PSF/SFU feeder at the bottom.

17. Vendor shall furnish GA drawing showing the following details for each MCC along with offer.
a. Overall dimensions of the panel.
b. Length of each shipping section
c. Height of each module
d. Cross, sectional view of panel showing busbar arrangement.
e. Foundation plan indicating size and gland plate
f. Weight of each shipping section

Wednesday, 10 January 2018

SWITCH DISCONNECTOR FUSE

1. General

1.1. Switches should be tested for disconnection function and to be called as switch disconnetor fuse.
1.2. The switches will conform to the requirements of IEC 947.1 and IEC 947-3 & IS 13947 part 1 and part 3
− the switches will have an impulse withstand voltage of 8 kV.
− the switches will have a rated operational voltage of 660V AC (50/60 Hz)
− the switches will have a short circuit withstand current (Icw) for 1 second of 2 kA for ratings up to 63A, 5kA up to 200A and 10kA beyond 200A upto 630A.
1.3. The switches will be of the positive contact indication type (according to IEC 947 – 3) to the exclusion of all other mechanisms. This function is to be certified by tests carried out by the constructor.
1.4. The range of switches will be available in 3 and 4 pole versions with full rated fused switched neutral within the same frame size.

2. Construction and operation

2.1. The switch operating mechanism will ensure rapid opening and closing (operator independent) and will conform to §2-12 of IEC 947-3. The closing of all poles, including the neutral, will be simultaneous as required by IEC 947-3.
2.2. To ensure positive contact indication as described in IEC 947-3 § 7-2-7.
− The operating handle will only indicate the O (OFF) position if the main contacts are actually separated. They will be achieved by design of the operating mechanism.
− The switches will be designed to be locked on the OFF position by padlock (with locking in
the ON position possible)
− The distance between open contacts will be greater than 8 mm.
2.3. Fuses should be isolated from both sides. Construction should prevent the possibility of live outgoing when incoming is live but there is no fuse mounted on the switch.
− These auxiliary contacts will be common with all of the range.
− The auxiliary contacts can easily be mounted on site without taking out any part like side
plate etc. and disturbing the mechanism.
2.4. The electrical endurance will be that of category A. It will correspond to an AC23 operational category without a current derating at 415V ac for ratings up to 630A.
2.5. Fuse should be stationery during the switch operation.

3. Contact system

3.1. Contact system should have self wiping feature.
3.2. Separate arcing and current carrying zone to be provided for better thermal performance throughout the life of the switch.
3.3. Contact system should be designed in such a way that during high short circuit fault current the contact pressure increases and switch can withstand the fault. In no circumstances there shall be any repulsion between the contacts during short circuit

4. Installation and auxiliaries

4.1. The switches can be panel mounted.
4.2. The switches should come along with an operating handle with door interlock with defeat and padlock as standard.
4.3. Phase barriers for all switches should be available as standard. Terminal shield upto 63A should be available as standard. For higher ratings provision for fitment should be available.
4.4. Length of operating shaft should be adjustable continuously. This feature should come as a standard.
4.5. The switches should be able to take Aluminum termination.

5. Maintenance and site convertibility

5.1. The switches should be modular type. In case a single pole is damaged it should be possible to replace the entire pole instead of replacing the contacts inside.
5.2. It should be possible to convert 3 Pole to 4 Pole switch and vice versa.
5.3. In case it is required it should be possible to convert a switch from BS type fuse holder to DIN type fuse holder and vice versa at site

Monday, 1 January 2018

Contactor Selection for Motors with long starting time

This note explains contactor selection for motors with long starting time. The note has been divided into three parts for easy understanding of the concepts involved. They are as follows,
1. Understanding Motor Inrush Current
2. Long Starting Time Applications
3. Contactor selection for motors with long starting time

Understanding Motor Inrush Current (Stator current)
A motor generally drives a load through some transmission system. During start, the motor draws a high starting current or inrush current. This current is about 6-8 times the motor rated current and can cause a significant voltage drop. This voltage fluctuation affects other devices connected to the same supply. Hence several other strategies are employed for starting motors to reduce its starting current; the most commonly employed being the Star–Delta starting. The starting value of the current is independent of the load attached; however it must be sufficient to overcome the inertia of the motor load system. However, inertia of the load impacts the starting time of the motor as explained in the next part. As the motor accelerates and nears its rated speed, the current gradually reduces and
settles down to a value equal to motor rated current or less depending on the actual load connected. The typical torque-speed characteristics of an induction motor are as given below,

Long Starting Time Applications
The total time from rest till the motor draws its rated current is called the starting time. The starting time of the motor is a function of the load inertia, load speed and the starting torque developed by the motor. A high inertia load requires an extended time to reach full speed and hence the motor also draws high starting current for a long time. The motor starting time is specified by the manufacturer in the motor data sheet. Since motor starting time is also a function of applied voltage it differs for different starting methods. For example starting time of the motor with Direct-Online starting would be different than with Star-Delta starting. The starting line current in Star Delta configuration is one third of the starting current of the same motor in DOL configuration. However applied voltage and therefore starting torque also reduces, leading to higher starting time

Long starting time applications are generally those applications in which the motor starting time is around 40 to120 secs.
Typical applications involving motors with a high starting time are,
• Induced Draft Fans (ID Fans)
• Forced Draft Fans (FD Fans)
ID and FD fans have a high inertia and hence motors required to drive them will have a long starting time. As a result the motor will draw high inrush current for an extended period of time.

The high inrush current drawn by the motor at start is carried by the contactors that are used for switching. Since, this current flows for an extended period of time, the contactor needs to be selected judiciously. Guidelines for selection of contactor rating is as follows:

Contactor Selection for motors with long starting time

Contactors are selected based on their overload current withstand capability. Overload withstand capability is defined in IEC 60947-4-1.

It means that a contactor with rated operational current equal to or less than 630A can withstand 8 times its rated Ac3 operational current for a period of 10 seconds. This rating is also called as the 10 sec rating of the contactors.

For Example:
Let Rated operational current (AC3 Utilization category) of contactor = 400A.
Then the maximum current it can carry for a period of 10 sec = 8 x I = 3200A e
Now let us look at an example, how to arrive at minimum AC3 Ratings of the Star, Main and Delta contactors

Motor specifications
Motor kW Rating: 160 kW
Motor Full Load Line Current: 304A
Motor Starting time in Star-Delta: 85 sec

Solution:
Delta contactor can be directly selected as per type 2 chart specified by the contactor manufacturer. This is because delta contactor is connected only when the motor has reached near its rated speed and motor current has reduced to its full load value


Utilization categories

Contactors are most commonly used in applications concerning control of electric motors. Contactors are used to start, stop, reverse, jog and plug the motors depending upon the application requirement. Contactors along with thermal overload relays also provide protection to the motor against overloads.

The most basic data required for contactor selection is the motor HP rating and it’s rated current. However this data is alone not sufficient. The type of load, duty cycle of the load, switching frequency are some of the factors that influence contactor selection. The switching capability of contactors is majorly dependent on the type of application, and hence international standards (IEC 60947-4-1) specify utilization categories which cover a broad range of applications. These utilization categories and the data associated with them are used by manufacturers to establish contactor ratings.

The utilization categories as per IEC 60947-4-1 are as follow:

AC-1 : Non-inductive or slightly inductive loads, resistance furnaces
AC-2 : Slip-ring motors : starting, switching off
AC-3 : Squirrel-cage motors : starting, switching off motors during running 1)
AC-4 : Squirrel-cage motors : starting, plugging, inching
AC-5a : Switching of electric discharge lamp controls
AC-5b : Switching of incandescent lamps
AC-6a : Switching of transformers
AC-6b : Switching of capacitor banks
AC-7a : Slightly inductive loads in household appliances and similar applications
AC-7b : Motor loads for household applications
AC-8a : Hermetic refrigerant compressor motor to control with manual resetting of overload release
AC-8b : Hermetic refrigerant compressor motor to control with automatic resetting of overload release
AC-15 : Control of a.c electromagnetic lods
DC-1 : Non-inductive or slightly inductive loads, resistance furnace
DC-3 : Shunt-motors : Starting, Plugging, Inching
Dynamic braking of dc motors
DC-5 : Series-motors : Starting, Plugging, Inching
Dynamic braking of dc motors
DC-6 : Switching of incandescent lamps

1) AC-3 category may be used for occasional inching (jogging) or plugging for limited time periods such as machine set-up: during limited time periods, the number of such operations should not exceed five per minute or more than 10 in a ten minute period.

2) A hermetic refrigerant compressor motor is a combination consisting of a compressor and a motor, both of which are enclosed in the same housing, with no external shaft or shaft seals, the motor operating in the refrigerant. 

The utilization categories most commonly encountered in contactor applications are AC-3 & AC-4

Applications under utilization category AC-3 (Normal Switching) are: Compressors, Pumps, Fans, Conveyors, Mixers, Agitators, Air conditioners, Elevators etc

Applications under utilization category AC-4 (Plugging, inching) are: Printing presses, Wire drawing machines, Centrifuges etc

The making and breaking capacities of contactors are dependent on the utilization categories and the standard specifies that the contactors or starters shall be capable of making and breaking currents without failure under the conditions stated.

Over voltage causes and effects

Over voltages or surges in the power system are the abrupt rise in the voltage level in the system. There could be several reasons for over voltage. The normal operating voltage of the system do not stress the insulation severely. But the voltage stresses due to over voltages can be so high that they may become dangerous to both the cables and the connected equipment and may cause damage, unless some protective measure against over voltages are taken. Over voltages occurrence in the system can be categorized by reasons:

1. External over voltages:

These over voltage originate from the atmospheric disturbances, mainly due to lightning. These over voltages take the form of a unidirectional impulse whose maximum possible amplitude has no direct relation with the operating voltage of the system. They may be due to any one of the following causes.
a. Direct lightning stroke
b. Electromagnetically  induced voltages due to lightning discharge near the line
c. Voltage induced due to the changing atmospheric condition along the transmission line
d. Electrostatic ally induced over voltages due to presence of the charge clouds 
e. Due to friction of the charged particles like dust, snow in the atmosphere or due to change in the altitude of the line. 

2. Internal over voltages:

Caused due to changes in operating conditions of the network, further classifieds into two groups.

a. Switching or transient over voltages
    The over voltages are generally of oscillatory nature caused by transient phenomena which appears when the state of network is changed by switching operations or fault condition.
The frequency of oscillation is governed by the inherent inductance and capacitance of the system and may very from few hundres Hz to few kHz

b. Steady state or temporary over voltages
    These are over voltages developed due to the disconnection of loads at power frequency.
 



Wednesday, 6 December 2017

IP Rating

IP Rating:
Rating
Protection from Solids
Protection from Liquids
IP00
No protection
No protection
IP01
No protection
condensation
IP02
No protection
water spray < 15 degrees from vertical
IP03
No protection
water spray < 60 degrees from vertical
IP04
No protection
water spray from any direction
IP05
No protection
low pressure water jets from any direction
IP06
No protection
high pressure water jets from any direction
IP07
No protection
temporary immersion to at least 1m from bottom and 15cm from top of object
IP08
No protection
continuous immersion to a specified depth or pressure
IP10
touch by hands (>50mm)
No protection
IP11
touch by hands (>50mm)
condensation
IP12
touch by hands (>50mm)
water spray < 15 degrees from vertical
IP13
touch by hands (>50mm)
water spray < 60 degrees from vertical
IP14
touch by hands (>50mm)
water spray from any direction
IP15
touch by hands (>50mm)
low pressure water jets from any direction
IP16
touch by hands (>50mm)
high pressure water jets from any direction
IP17
touch by hands (>50mm)
temporary immersion to at least 1m from bottom and 15cm from top of object
IP18
touch by hands (>50mm)
continuous immersion to a specified depth or pressure
IP20
touch by fingers (>12.5mm)
No protection
IP21
touch by fingers (>12.5mm)
condensation
IP22
touch by fingers (>12.5mm)
water spray < 15 degrees from vertical
IP23
touch by fingers (>12.5mm)
water spray < 60 degrees from vertical
IP24
touch by fingers (>12.5mm)
water spray from any direction
IP25
touch by fingers (>12.5mm)
low pressure water jets from any direction
IP26
touch by fingers (>12.5mm)
high pressure water jets from any direction
IP27
touch by fingers (>12.5mm)
temporary immersion to at least 1m from bottom and 15cm from top of object
IP28
touch by fingers (>12.5mm)
continuous immersion to a specified depth or pressure
IP30
tools & wires (>2.5mm)
No protection
IP31
tools & wires (>2.5mm)
condensation
IP32
tools & wires (>2.5mm)
water spray < 15 degrees from vertical
IP33
tools & wires (>2.5mm)
water spray < 60 degrees from vertical
IP34
tools & wires (>2.5mm)
water spray from any direction
IP35
tools & wires (>2.5mm)
low pressure water jets from any direction
IP36
tools & wires (>2.5mm)
high pressure water jets from any direction
IP37
tools & wires (>2.5mm)
temporary immersion to at least 1m from bottom and 15cm from top of object
IP38
tools & wires (>2.5mm)
continuous immersion to a specified depth or pressure
IP40
tools & small wires (>1mm)
No protection
IP41
tools & small wires (>1mm)
condensation
IP42
tools & small wires (>1mm)
water spray < 15 degrees from vertical
IP43
tools & small wires (>1mm)
water spray < 60 degrees from vertical
IP44
tools & small wires (>1mm)
water spray from any direction
IP45
tools & small wires (>1mm)
low pressure water jets from any direction
IP46
tools & small wires (>1mm)
high pressure water jets from any direction
IP47
tools & small wires (>1mm)
temporary immersion to at least 1m from bottom and 15cm from top of object
IP48
tools & small wires (>1mm)
continuous immersion to a specified depth or pressure
IP50
Limited dust ingress protection
No protection
IP51
Limited dust ingress protection
condensation
IP52
Limited dust ingress protection
water spray < 15 degrees from vertical
IP53
Limited dust ingress protection
water spray < 60 degrees from vertical
IP54
Limited dust ingress protection
water spray from any direction
IP55
Limited dust ingress protection
low pressure water jets from any direction
IP56
Limited dust ingress protection
high pressure water jets from any direction
IP57
Limited dust ingress protection
temporary immersion to at least 1m from bottom and 15cm from top of object
IP58
Limited dust ingress protection
continuous immersion to a specified depth or pressure
IP60
Total dust ingress protection
No protection
IP61
Total dust ingress protection
condensation
IP62
Total dust ingress protection
water spray < 15 degrees from vertical
IP63
Total dust ingress protection
water spray < 60 degrees from vertical
IP64
Total dust ingress protection
water spray from any direction
IP65
Total dust ingress protection
low pressure water jets from any direction
IP66
Total dust ingress protection
high pressure water jets from any direction
IP67
Total dust ingress protection
temporary immersion to at least 1m from bottom and 15cm from top of object
IP68
Total dust ingress protection
continuous immersion to a specified depth or pressure
IP69K
Total dust ingress protection
steam jet cleaning

IP55 time duration
How much time can equipment with ip 55 should stand rain water without problem?
There is a minimum time of at least 15 minutes, which is used for testing purposes, but we would suggest a product should be designed and tested for the intended purpose rather than a particular IP rating. You can then have a third party test the design to see what IP rating it meets.
IPW55 vs IP55
What is the difference between IP55 and IPW55 protection?
The “W” in IPW 55 signifies that the rating includes weather conditions.  e.g. rain, condensation and humidity.
IP55
·         Limited dust ingress protection.
·         Protected against low pressure water jets from any direction.

IPW55
·         Limited dust ingress protection.
·         Protected against low pressure water jets from any direction.
·         Protected against damp and wet weather.

Condensation protection (IP21)
What is meant by protected against condensation as part of an IP21 rating?
When the surface temperature of a device is lower than the dew point temperature (the temperature at which air cannot hold any more water) moisture will begin to collect on the device.
For example, condensation will form if you take a device that has been sitting in a cool environment such as an air conditioned room and move it to a hot and humid outdoor environment.
If a device has an IP21 rating it will be protected from damage due to any buildup of moisture on surfaces which are in contact with the air.
Sensitive components such as electronic devices are protected from condensation by coating the surface with a waterproof barrier such as a conformal coating.
IP23S vs IP23
What is the difference between IP23 and IP23S, and which has a more stringent testing criteria?
The ‘S’ means ‘Device standing still during water test’. IP23 is considered more stringent than IP23S, since it covers this and IP23M which means ‘Device moving during water test’.
D meaning in IP23D
I have a heat detector for a fire alarm system and I have been told it is ip23d, can you please let me know what the‘d’ is?
It is additional to the IP23 rating, and relates to protection against a wire touching hazardous parts.  For futher information see IP codes explained and additional IP code letters.
B meaning e.g. IP43B
What is the meaning of the ‘B’ in IP41B?
The “B” means: Protected against access to hazardous parts with a finger